Part 21 Report - 1997-571
ACCESSION #: 9708250224
NSD-NRC-97-5267
Westinghouse Energy Systems Nuclear Services Division
Electric Corporation
Box 355
Pittsburgh Pennsylvania 15230-
0355
August 19, 1997
U.S. Nuclear Regulatory Commission
ATTN: Document Control Desk
Washington, DC 20555-0001
Attention: NRC Operations Center
Subject: Notification of the Potential Existence of Defects Pursuant to
10CFR21.21
Westinghouse has identified a possible defect in a basic component that
could potentially create a substantial safety hazard and therefore is
deemed reportable under 10CFR21.21.
Background/Evaluation
Three HMCP (Motor Circuit Protectors) molded case circuit breakers were
recently returned to Westinghouse's vendor, Cutler-Hammer when the
utility determined that some of the poles were tripping outside the
setpoint calibration range. These breakers were verified to be within
specification before shipment as part of the Westinghouse commercial
dedication process, but two tested out of specification before
installation at the plant and one tripped in service when the motor was
started. All were found with at least one pole out of specification when
returned.
HMCP Series C breakers, through magnetic trip action, provide
instantaneous short circuit protection for motor circuits. These
breakers have ratings from 3 amps to 600 amps in three frame sizes. The
three breakers returned were all 400 amp.
Safety Significance
The setpoint on an HMCP breaker is selected to provide circuit protection
without tripping on motor starting current. Several trip ranges are
available for selection on each breaker. If the setpoint is not within
the selected range, the possibility exists that the circuit will open
preventing a safety-related motor from starting. However, confidence in
continued system performance can be established by a history of
successful motor start tests even if the breaker was not tested at the
plant prior to installation.
Plant Applicability
The recommended actions apply to all plants that utilize these breakers
for safety-related motor circuits.
[Illegible]
NSD-NRC-97-5267 2 August 19, 1997
Recommendations/Corrective Action
Although setpoints of HMCP breakers are verified during the commercial
dedication process, Westinghouse will recommend that the setpoint for
breakers in safety-related motor circuits be verified prior to
installation at the plants in addition to periodic surveillance testing.
Limited feedback from utilities indicates that this verification is a
typical practice.
If you have any questions regarding the notification, please call me at
412/374-5282.
Sincerely,
H. A. Sepp, Manager
Regulatory and Licensing Engineering
2508C-RBM-2:081197
*** END OF DOCUMENT ***
Page Last Reviewed/Updated Tuesday, March 09, 2021