Part 21 Report - 1997-572

ACCESSION #: 9709230255 NSD-NRC-97-5330 Westinghouse Energy Systems Nuclear Services Division Electric Corporation Box 355 Pittsburgh Pennsylvania 15230-0355 September 18, 1997 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 ATTN: NRC Operations Center Subject: Follow-up to Notification of the Potential Existence of Defects Pursuant to 10CFR 21.21 Westinghouse provided a Notification of the Potential Existence of Defects Pursuant to 10CFR 21.21 regarding HMCP (Motor Circuit Protectors) molded case circuit breakers on August 19, 1997 via NSD-NRC-97-5267. Attached, with the original notification is a Nuclear Safety Advisory Letter (NSAL-97-007, dated 9/17/97) which transmitted recommendations regarding this issue to potentially impacted plans. The plants are identified in the NSAL. If you have any questions regarding this information, please call me at 412/374-5292. Sincerely, H. A. Sepp, Manager Regulatory and Licensing Engineering /p Attachment "The mission of NSD is to provide our customers with people, equipment and services that set the standards of excellence in the nuclear industry." 2536C-RBM-1:091897 Westinghouse NUCLEAR SAFETY ADVISORY LETTER Energy Systems Business Unit THIS IS A NOTIFICATION OF A RECENTLY IDENTIFIED POTENTIAL SAFETY ISSUE PERTAINING TO BASIC COMPONENTS SUPPLIED BY WESTINGHOUSE. THIS INFORMATION IS BEING PROVIDED TO YOU SO THAT A REVIEW OF THIS ISSUE CAN BE CONDUCTED BY YOU TO DETERMINE IF ANY ACTION IS REQUIRED. P.O. Box 355, Pittsburgh, PA 15230-0355 Subject: Breaker Trip Settings Number: NSAL-97-007 Basic Component: HMCP Molded Case Circuit Breakers Date: 9/17/97 Plants: See Sheet 3 Substantial Safety Hazard of Failure to Comply Pursuant to 10 CFR 21.21(a) Yes [x] No [ ] Transfer of Information Pursuant to 10 CFR 21.21(b) Yes [ ] Advisory Information Pursuant to 10 CFR 21.21(d)(2) Yes [ ] Reference: NSD-NRC-97-5267, 8/19/97 SUMMARY Three HMCP (Motor Circuit Protectors) molded case circuit breakers were returned when a utility determined that some of the poles were tripping outside the specified range. The settings had been verified through a commercial dedication process. This issue was reported to the NRC pursuant to 10 CFR Part 21 (copy attached). Recommendations for on-site testing are provided. Additional information, if required, may be obtained from the originator. Telephone 412-374-5953. Originator(s): R. B. Miller H. A. Sepp, Manager Regulatory & Licensing Regulatory & Licensing Engineering Engineering 1810A/NSAL-97-00 Sheet 1 of 3 ISSUE DESCRIPTION Three HMCP (Motor Circuit Protectors) molded case circuit breakers were recently returned to Westinghouse's vendor, Cutler-Hammer when the utility determined that some of the poles were tripping outside the setpoint calibration range. These breakers were verified to be within specification before shipment as part of the Westinghouse commercial dedication process, but two tested out of specification before installation at the plant and one tripped in service when the motor was started. All were found with at least one pole out of specification when returned. TECHNICAL EVALUATION HMCP Series C breakers, through magnetic trip action, provide instantaneous short circuit protection for motor circuits. These breakers have ratings from 3 amps to 600 amps in three frame sizes, The three breakers returned were all 400 amp, but there is no evidence that limits the issues to this, size breaker. The breakers am tested at the lowest setting and the highest setting as part of the commercial dedication process. Intermediate settings are not tested during the commercial dedication process. The returned breakers were verified to be out of specification at the low and high setting positions. Although many utilities will perform a verification test before installation, Westinghouse has not included this as part of maintenance recommendations. ASSESSMENT OF SAFETY SIGNIFICANCE The setpoint on a HMCP breaker is selected to provide circuit protection without tripping on motor starting current. Several trip ranges are available for selection on each breaker. If the setpoint is not within the selected range, the possibility exists that the circuit will open preventing a safety-related motor from starting. Westinghouse determined that this issue could potentially create a substantial safety hazard and therefore reported it under 10 CFR Part 21, Confidence in continued system performance can be established by a history of successful motor start tests even if the breaker was not tested at the plant prior to installation. RECOMMENDED ACTIONS Westinghouse recommends that the setpoint selected on the HMCP breakers be verified prior to installation in addition to periodic surveillance testing. Each pole should be tested separately. It is not recommended that the breakers be tested with all poles in series since all pole trip actuators would be exerting a force on the trip bar at the same time, which could result in tripping at a lower current. 1810A/NSAL-97-00 Sheet 2 of 3 POTENTIALLY AFFECTED PLANTS H. B. Robinson Unit 2 Shearon Harris Haddam Neck McGuire Units 1 & 2 Catawba Units 1 & 2 Turkey Point Unit 3 Wolf Creek Callaway Point Beach Unit 1 Yonggwang Units 1 & 2 Maanshan Units 1 & 2 Crystal River Unit 3 Three Mile Island Unit 1 Chinshan Units 1 & 2 Brunswick Units 1 & 2 Peach Bottom Units 2 & 3 Vermont Yankee Kuosheng Unit 2 Laguna Verde Units 1 & 2 1810A/NSAL-97-00 Sheet 3 of 3 *** END OF DOCUMENT ***

Page Last Reviewed/Updated Tuesday, March 09, 2021