Part 21 Report - 1998-100
ACCESSION #: 9801160158
POWER REACTOR | | EVENT NUMBER: | 33535 |
FACILITY: INDIAN POINT | REGION: 1 | NOTIFICATION DATE: | 01/14/98 |
UNIT: [2] [ ] [ ] | STATE: NY | NOTIFICATION TIME: | 17:08 (ET] |
RX TYPE: | [2] W-4-LP, [3] W-4-LP | EVENT DATE: | 01/14/98 |
| | EVENT TIME: | 15:00[EST] |
NRC NOTIFIED BY: | PHIL SANTIANI | LAST UPDATE DATE: | 01/14/98 |
HQ OPS OFFICER: | DICK JOLLIFFE | | |
| NOTIFICATIONS | | |
EMERGENCY CLASS: | NOT APPLICABLE | | |
10 CFR SECTION: | JOHN ROGGE | RDO | |
CDEG 21.21(c)(3)(i) | DEFECTS/NONCOMPLIANCE | | |
| | VERN HODGE | NRR |
UNIT | SCRAM CODE | RX CRIT | INIT PWR | INIT RX MODE | CURR PWR | CURR RX MODE |
2 | N | N | 0 | COLD SHUTDOWN | 0 | COLD SHUTDOWN |
EVENT TEXT
- 10CFR PART 21 REPORT -
FOUR SAFETY-RELATED 480-VOLT WESTINGHOUSE MODEL #DB-50 CIRCUIT BREAKERS WERE SENT TO NUCLEAR LOGISTICS, INC, FT WORTH, TEXAS, AN APPROVED 10CFR50, APPENDIX B QUALIFIED REPAIR FACILITY, FOR OVERHAUL. THE BREAKERS WERE RETURNED TO UNIT 2 OUTSIDE THE MANUFACTURER'S TOLERANCES AND NOT MEETING THE REQUIREMENTS OF THE LICENSEE CLASS "A" (SAFETY- RELATED) PURCHASE ORDER.
THIS CONDITION WAS DISCOVERED DURING PRE-INSTALLATION TESTING BEFORE THE BREAKERS WERE INSTALLED IN UNIT 2. IF INSTALLED, THESE BREAKERS MIGHT HAVE MALFUNCTIONED WHEN CALLED UPON TO PERFORM THEIR SAFETY-RELATED FUNCTION.
THE LICENSEE PLANS TO REPAIR AND TEST THESE BREAKERS (AND THE REMAINING 46 SAFETY-RELATED 480-VOLT BREAKERS) ON-SITE PRIOR TO INSTALLATION.
THE LICENSEE PLANS TO SUBMIT A WRITTEN PART 21 REPORT TO THE NRC.
THE LICENSEE WILL INFORM THE NRC RESIDENT INSPECTOR.
Attachment "CITRS Event Detail Report"(33535)
*** END OF DOCUMENT ***
Page Last Reviewed/Updated Tuesday, March 09, 2021