Part 21 Report - 1998-190

LICENSEE: NIAGARA MOHAWK POWER CORP. SITE: NINE MILE POINT 2 EN NUMBER:33650 DOCKET: 05000410 EVENT DATE: 02-04-98 RX TYPE: BWR EVENT TIME: 13:50 VENDORS: GE-5 NOTIFY DATE: 02-04-98 EMERGENCY CLASS: N/A REGION: 1 STATE: NY TIME: 13:50 OPS OFFICER: JOHN MacKINNON 10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 2 N Y 95 POWER OPERATION 95 POWER OPERATION 10 CFR PART 21: LOCKUP OF WESTRONICS RECORDERS DUE TO SERVO AMPLIFIER BOARD OVERRANGE FEATURE - THIS PROBLEM WAS CORRECTED IN THE FALL OF 1997. DESCRIPTION OF CONDITION: THE DEVIATION DESCRIBED IN THE REFERENCED DEVIATION EVENT REPORTS (DER) AFFECTS THE FIVE SAFETY-RELATED (SR) RECORDERS. RECORDERS 2ISC*LR1623A/B AND 2ISC*PR1623A/B WERE SUPPLIED TO GENERAL ELECTRIC (GE) BY WESTRONICS AS NON-SAFETY-RELATED INSTRUMENTS (NSR) AND WERE UPGRADED TO SR BY GE (PURCHASE ORDER/SPEC. P800A). FUEL ZONE LEVEL RECORDER 2ISC*LR1615 WAS SUPPLIED AS SR EQUIPMENT AND IS FED FROM TRANSMITTER 2ISC*LT13B. THE WIDE RANGE LEVEL RECORDERS 2ISC*LR1623A/B ARE FED FROM TRANSMITTERS 2ISC*LT9A/B. THE LATTER RECORDERS EACH ALSO DISPLAY VESSEL PRESSURE ON A SECOND CHANNEL AND PEN. THE PRESSURE CHANNELS 2ISC*PR1623A/B ARE FED FROM PRESSURE TRANSMITTERS 2ISC*PT16A/B. ALL OF THE AFFECTED RECORDERS ARE ON MAIN CONTROL ROOM PANEL 2CEC*PNL601. ALL OF THESE RECORDERS ARE SR TECHNICAL SPECIFICATIONS POST-ACCIDENT MONITORING INSTRUMENTS. THEY ARE IDENTIFIED ON THE NMP2 MASTER EQUIPMENT LIST AS REGULATORY GUIDE 1.97 MONITORING EQUIPMENT. ALL OF THE ABOVE MENTIONED RECORDERS WERE INSTALLED WHEN THE PLANT WAS INITIALLY LICENSED. DERs 2-97-1662 AND 2-97-3030 DESCRIBE FAILURES OF THE AFFECTED VESSEL PRESSURE AND LEVEL RECORDERS LISTED ABOVE SUCH THAT THE AFFECTED RECORDER CHANNEL LOCKS UP TEMPORARILY UNDER CONDITIONS WHERE THEY EXPERIENCE A LARGE STEP CHANGE IN THE PROCESS VARIABLE MONITORED OR WHEN THE RECORDERS HAVE THE PEN MANUALLY MOVED FROM THE POSITION TO WHICH IT WAS DRIVEN BY THE SERVO AMPLIFIER BOARD (WESTRONICS PART NUMBER CB100124N04). ALL OF THE POTENTIALLY AFFECTED RECORDERS NOW ARE (AS OF THE FALL OF 1997) NOW EQUIPPED WITH THE NEWER SERVO AMPLIFIER BOARDS. THESE BOARDS HAVE AN INHERENT TIME DELAY THAT ALLOWS THE BOARD TO FUNCTION UNDER TRANSIENT CONDITIONS WITHOUT LOCKING UP. THERE HAVE BEEN NO FURTHER FAILURES (OF THE TYPE DESCRIBED) EXPERIENCED SINCE THE INSTALLATION OF THE NEW BOARDS. THEREFORE, NO FURTHER MAINTENANCE ACTION IS REQUIRED WITH RESPECT TO THESE RECORDERS. PROCUREMENT PERSONNEL HAVE VERIFIED THAT NONE OF THE OLDER MODEL BOARDS ARE BEING UTILIZED AT NINE MILE POINT UNIT 1 OR ARE BEING MAINTAINED AS SPARES. LICENSEE: NIAGARA MOHAWK POWER CORP. SITE: NINE MILE POINT 2 EN NUMBER:33650 DOCKET: 05000410 EVENT DATE: 02-04-98 RX TYPE: BWR EVENT TIME: 13:50 VENDORS: GE-5 NOTIFY DATE: 02-04-98 EMERGENCY CLASS: N/A REGION: 1 STATE: NY TIME: 13:50 OPS OFFICER: JOHN MacKINNON 10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 2 N Y 95 POWER OPERATION 95 POWER OPERATION 10 CFR PART 21: LOCKUP OF WESTRONICS RECORDERS DUE TO SERVO AMPLIFIER BOARD OVERRANGE FEATURE - THIS PROBLEM WAS CORRECTED IN THE FALL OF 1997. DESCRIPTION OF CONDITION: THE DEVIATION DESCRIBED IN THE REFERENCED DEVIATION EVENT REPORTS (DER) AFFECTS THE FIVE SAFETY-RELATED (SR) RECORDERS. RECORDERS 2ISC*LR1623A/B AND 2ISC*PR1623A/B WERE SUPPLIED TO GENERAL ELECTRIC (GE) BY WESTRONICS AS NON-SAFETY-RELATED INSTRUMENTS (NSR) AND WERE UPGRADED TO SR BY GE (PURCHASE ORDER/SPEC. P800A). FUEL ZONE LEVEL RECORDER 2ISC*LR1615 WAS SUPPLIED AS SR EQUIPMENT AND IS FED FROM TRANSMITTER 2ISC*LT13B. THE WIDE RANGE LEVEL RECORDERS 2ISC*LR1623A/B ARE FED FROM TRANSMITTERS 2ISC*LT9A/B. THE LATTER RECORDERS EACH ALSO DISPLAY VESSEL PRESSURE ON A SECOND CHANNEL AND PEN. THE PRESSURE CHANNELS 2ISC*PR1623A/B ARE FED FROM PRESSURE TRANSMITTERS 2ISC*PT16A/B. ALL OF THE AFFECTED RECORDERS ARE ON MAIN CONTROL ROOM PANEL 2CEC*PNL601. ALL OF THESE RECORDERS ARE SR TECHNICAL SPECIFICATIONS POST-ACCIDENT MONITORING INSTRUMENTS. THEY ARE IDENTIFIED ON THE NMP2 MASTER EQUIPMENT LIST AS REGULATORY GUIDE 1.97 MONITORING EQUIPMENT. ALL OF THE ABOVE MENTIONED RECORDERS WERE INSTALLED WHEN THE PLANT WAS INITIALLY LICENSED. DERs 2-97-1662 AND 2-97-3030 DESCRIBE FAILURES OF THE AFFECTED VESSEL PRESSURE AND LEVEL RECORDERS LISTED ABOVE SUCH THAT THE AFFECTED RECORDER CHANNEL LOCKS UP TEMPORARILY UNDER CONDITIONS WHERE THEY EXPERIENCE A LARGE STEP CHANGE IN THE PROCESS VARIABLE MONITORED OR WHEN THE RECORDERS HAVE THE PEN MANUALLY MOVED FROM THE POSITION TO WHICH IT WAS DRIVEN BY THE SERVO AMPLIFIER BOARD (WESTRONICS PART NUMBER CB100124N04). ALL OF THE POTENTIALLY AFFECTED RECORDERS NOW ARE (AS OF THE FALL OF 1997) NOW EQUIPPED WITH THE NEWER SERVO AMPLIFIER BOARDS. THESE BOARDS HAVE AN INHERENT TIME DELAY THAT ALLOWS THE BOARD TO FUNCTION UNDER TRANSIENT CONDITIONS WITHOUT LOCKING UP. THERE HAVE BEEN NO FURTHER FAILURES (OF THE TYPE DESCRIBED) EXPERIENCED SINCE THE INSTALLATION OF THE NEW BOARDS. THEREFORE, NO FURTHER MAINTENANCE ACTION IS REQUIRED WITH RESPECT TO THESE RECORDERS. PROCUREMENT PERSONNEL HAVE VERIFIED THAT NONE OF THE OLDER MODEL BOARDS ARE BEING UTILIZED AT NINE MILE POINT UNIT 1 OR ARE BEING MAINTAINED AS SPARES.

Page Last Reviewed/Updated Tuesday, March 09, 2021