Part 21 Report - 1998-200
LICENSEE: ILLINOIS POWER CO.
SITE: CLINTON 1 EN NUMBER:33668
DOCKET: 05000461 EVENT DATE: 02-06-98
RX TYPE: BWR EVENT TIME: 00:00
VENDORS: GE-6 NOTIFY DATE: 02-06-98
EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 11:23
OPS OFFICER: CHAUNCEY GOULD
10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH
UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE
CODE CRIT PWR PWR
1 N N 0 REFUELING 0 REFUELING
10CFR PART 21 REPORT -
THE LICENSEE INITIATED CONDITION REPORT #1-97-12-165 DUE TO OIL
LEAKING AROUND THE DIAPHRAGM OF A REPLACEMENT PRESSURE
REDUCING/DUMP VALVE (PART
#NS108916A) INSTALLED ON AN ITT BARTON HYDRAMOTOR ACTUATOR. THIS
WAS DISCOVERED PRIOR TO DECLARING THE HYDRAMOTOR OPERABLE DURING
POST MAINTENANCE TESTING OF THE HYDRAMOTOR TO DETERMINE IF THE
ASSOCIATED DAMPER MET ITS REQUIRED CLOSING TIME. HYDRAMOTORS ARE
USED AT CLINTON TO OPERATE SAFETY-RELATED DAMPERS IN VENTILATION
SYSTEMS. TWO ADDITIONAL PRESSURE REDUCING/DUMP VALVES WERE
REMOVED FROM THE STOREROOM AND BENCH TESTED WITH LEAKAGE
RESULTS
ON ONE OF THE VALVES BEING SIMILAR TO THE VALVE INSTALLED ON THE
HYDRAMOTOR IN THE PLANT. THE OTHER VALVE, HOWEVER, SUCCESSFULLY
PASSED THE TEST. FURTHER INVESTIGATION INTO THIS CONDITION
REVEALED
THAT THE PROBLEM WITH THE PRESSURE REDUCING/DUMP VALVE COULD
CAUSE THE HYDRAMOTOR TO CLOSE THE DAMPER SLOWER THAN THE DESIGN
TIME REQUIRED.
THIS IS CONTRARY TO THE PURCHASE SPECIFICATION FOR THE HYDRAMOTOR
WHICH SPECIFIES A REQUIRED DAMPER CLOSING TIME. THE 15 REMAINING
VALVES IN THE STOREROOM WILL ALSO BE TESTED.
ON THE BASIS THAT THE PRESSURE REDUCING/DUMP VALVE DOES NOT MEET
THE REQUIREMENT OF THE PROCUREMENT DOCUMENT AND THAT ITS
DEFICIENCY (WHICH APPEARS TO BE DUE TO POOR MACHINING OR
WORKMANSHIP) COULD CAUSE A SAFETY- RELATED ISOLATION DAMPER TO
MALFUNCTION, THE LICENSEE HAS CONCLUDED THAT THIS ISSUE IS A
10CFR PART 21.